agholding

Low Voltage(ACB Panel)

ACB Panel

Application Area

  • Utility power supply 400V system for MSB
  • Includes 3 CT for metering, 3 CTs for protection class wiring connection and ACB control accessories, with analog or digital |Ammeter and Volt meter
  • Includes Overcurent and earth fault protection as per customer request
  • Includes Bus bar terminal for incoming and outgoing cable connection

Motor Control COUNTRY OF ORIGIN (Japan/Italy)

  • Rated Service Voltage : 690V
  • Rated Insulation Voltage : 1000V
  • Rated Impulse Withstand Voltage : 12 KV
  • Frequency : 50,60
  • Rated Current: 800A to 6000A
  • Number of Pole : 3,4
  • Version: Fixed, Withdrawable
  • Isolation Behavior : IEC60947-3
  • Installation: Indoor/Outdoor
  • Control compartment : Yes
  • Future Extension : Yes
  • Control Voltage : 230V AC
  • Spring charging : 230VAC
  • Closing & Tripping control voltage : 230V AC

Enclosure And Structure

  • Standard Dimensions : 1700 H x 800/900/1000/1200 W x 800/1000 D ( 2 Doors )
  • Metal Sheet : EGI ( JFE , Japan)/Roll forming
  • Body Part thickness : 2mm
  • Door thickness : 1.5mm
  • Internal Partitions: IP 2X
  • Degree Of Protection Enclosure : IP 3X
  • Segregation form : Form 2/3/4
  • Mounting Method : Floor Standing
  • Cable Entry : Top entry (or) Buttom entry available on order

Busbar And Connecting Conductor

  • Busbar material : Tin Coated ( Oriental Copper, Thailand)
  • Busbar Joints : Tin plating

Painting & Color

  • External enclosure surfaces are first cleaned and pretreated for rust
  • Enclosure Color : Pebble Gray(RAL 7032), Light Gray(RAL 7305)
  • Epoxy Paint : Jotun , Norway

Discrepancy Switches

  • Indication Lamp – on/off/trip, Over current, Earth fault
  • CB, Position indicatorr