Low Voltage(ATS Panel)
ATS Panel
Application Area
- Utility power supply 400V system for MSB
- Includes 3 CT for metering, 3 CTs for protection class wiring connection and ATScontrol accessories, with analog or digital |Ammeter and Volt meter
- Includes Overcurent and earth fault protection as per customer request
- Includes Bus bar terminal for incoming and outgoing cable connection
ATS COUNTRY OF ORIGIN (Italy)
- Rated Service Voltage : 690V
- Rated Insulation Voltage : 1000V
- Rated Impulse Withstand Voltage : 12 KV
- Frequency : 50,60
- Rated Current : 125A to 2500A
- Number of Pole : 4
- Version: Fixed
- Isolation Behavior : IEC60947-3
- Installation : Indoor/Outdoor
- Control compartment : Yes
- Future Extension : Yes
- Control Voltage: 230V AC
Enclosure And Structure
- Standard Dimensions : 2000W x 1000H x 150 D
- Metal Sheet : EGI ( JFE , Japan)
- Body Part thickness : 1.5mm
- Door thickness : 1.2mm
- Internal Partitions : Yes
- Degree Of Protection Enclosure: Up to IP 3X(Optional IP 43)
- Segregation form : Up to Form 2b
- Mounting Type : Floor Standing/Wall mounting
- Cable Entry : By 3 phase socket
Busbar And Connecting Conductor
- Busbar material : Tin Coated ( Oriental Copper, Thailand)
- Busbar Joints : Tin plating
Painting & Color
- External enclosure surfaces are first cleaned and pretreated for rust
- Enclosure Color : Pebble Gray(RAL 7032), Light Gray(RAL 7305)
- Expoxy Paint : Jotun , Norway